New air cons fwd and aft main cabin fitted 27/10.
MRF submitted for fwd air con E49 (error) coming up, unit shutting down. Have run the fwd cabin aircon the last 2 days of swing and it has worked fine, still awaiting air con specialist to come and inspect. I have just been running that air con for the busy runs in the afternoon to avoid the Genset tripping or the error re occurring. Works fine when there is not much load on it.
Had problems with the generator getting overloaded literally every day between 3-4pm when Aircons are at max load. Genset trips and has to be switched back on. The breaker switch located on the red box, on the Genset has to switched back on and Aircons can be put back on but run at higher temp and less fan to avoid tripping again (21 degrees, speed 3 seems to keep the system at bay) Can run everything as normal for the rest of the day, just seems to get overloaded in the afternoons when aircon are working the hardest. MRF submitted. Aces have had a look and will be back to find the problem. Maintenance well aware of issue.
Replaced fwd and aft spring port side to, at CP3. Replaced fwd spring port side to, at CP1. New line for tying off boat also. All these lines that got replaced were well overdue.
24/10 Genset had 250hr service
⚡️ Check flagged emails. Important emails to read.
Have ordered truck wash, toilet duck and a metho sticker for the new spray bottle in this weeks stores.
Tams working on piles at CP3, just be aware they are on the edge of the pontoon when coming in to berth (still berth port side to the pontoon, just be aware they are working on the pontoon)